SAI-208D mother of the protection and control devices

1 . Function Deployment
Protection Model SAI-208DD
Three- phase overcurrent definite time √
Inverse phase overcurrent ( in general, very, extremely ) √
Overload alarm and trip protection √
Mother of the white charging protection √

2 . Description
2.1 Three- white overcurrent
The three sections of white over-current protection device is provided , Ⅰ, Ⅱ, Ⅲ fixed time limit, and white can also inverse time overcurrent protection . Either definite time or inverse time , each segment cast back control value (I1nf, I2nf, I3nf) can be controlled independently of each segment usage. Cast back control setpoint value means:
0 : Exit 1 : Inputs
Three sections with a soft white plate overcurrent protection , only soft plate and cast back into the control values ​​are given , the corresponding stages before investment.
2.1.1 Inverse time characteristics
White overcurrent protection characteristics selection setting Ifsx be selected for definite time or inverse time protection:
0 : Exit , 1,2,3 : Inverse time ( corresponding to the following ( 1 ) , ( 2 ) and ( 3) ) .
Choose to use one of the following three criteria inverse time characteristics . Inverse time characteristics for the current reference value IP and white inverse time protection current reference value Ii, tP inverse characteristic time constant for the white anti-time protection time constant tIi.
Normal inverse characteristics :

Very inverse characteristics :

Extremely inverse characteristics :

2.2 interphase charge protection
This unit has white charging protection , overcharge protection plate with a soft , protective cast while charging back with a white value Icdnf control . Only soft cast back plate and the control inputs are given value , the protection was put into . Icdnf values ​​have the following meanings :
0 : Exit 1 : Inputs
When charged the bus to an empty bus closing charge , if the mother has an empty failure to maintain system stability, need to quickly jump mother of the switch . Charging protection setting value on the more sensitive, very short delay in the outlet protection with a different value . In order to avoid system failure during normal operation so that the loss of selectivity malfunction , charging protection only after the mother of the switch from the open period of change together , this time by the user charging protection through automatic withdrawal limit tCD tuning, then automatically exit.
2.3 Overload protection
Overload protection device cast back control setpoint values ​​Igfhnf meaning :
0 : Exit 1 to 2: inputs - 1: Alarm , 2 : Trip
Overload trip protection features soft plate, pressure plate and throw only soft values ​​are given back control inputs , the corresponding trip protection only cast
Income ; overload alarm input control word can only generate an alarm event .
2.4 System abnormal condition alarm and lockout
2.4.1 Control loop break alarm
TWJ and HWJ same time is 1 or 0 , after the alarm delay .

3 . Device tuning
Including soft plate tuning device , the device settings and device parameters in three areas , see 3.1, 3.2 and 3.3 .
Tuning should follow the relevant regulations , the device has special requirements in the relevant notes. Device parameters without special needs , it is desirable default values ​​listed in the table . No protection, it should control the value to 0 - exit.
3.1 Soft- plate tuning device
Model
 
SAI-208DD
 
Three sections of white over-current protection
 

 
Overload trip protection
 

 
Mother of charge protection
 

 
Note : Soft plate only two values: inputs, quit. When the device is shipped , soft plate are tuning to quit.
3.2 Device setting value
No.
 
Name
 
Symbol
 
Tuning range
 
Remark
 
1
 
Phase
Between
Live
Flow
Insurance
Protect
 
Segment Ⅰ
 
Section Ⅰ white protective cast back control
 
I1nf
  
2
 
White segment Ⅰ current value
 
I1
 
0.5 ~ 100A
 
 
3
 
White segment Ⅰ delay setting
 
tI1
 
0.01 ~ 9.99S
 
 
4
 
Section Ⅱ
 
White protective cast back control section Ⅱ
 
I2nf
  
5
 
White Ⅱ segment current value
 
I2
 
0.5 ~ 100A
 
 
6
 
White Ⅱ segment delay value
 
tI2
 
0.01 ~ 9.99S
 
 
7
 
Ⅲ section
 
White protective cast back control section Ⅲ
 
I3nf
  
8
 
White Ⅲ segment current value
 
I3
 
0.5 ~ 100A
 
 
9
 
White Ⅲ segment delay value
 
tI3
 
0.01 ~ 99.99S
 
 
10
 
Inverse
 
White inverse time protection and value characteristics control
 
Ifsx
 
0-3
 
Note 1
 
11
 
White inverse time protection current reference value
 
Ii
 
0.5 ~ 100A
 
 
12
 
White anti-time protection time constant
 
tIi
 
0.1 ~ 99.99S
 
 
13
 
Public value
 
Low phase overcurrent closed lock value
 
ULbs
 
2 ~ 120V
 
Invalid
 
14
 
Overload
Protection
 
Overload protection cast back control
 
Igfhnf
 
0-2
 
Note 2
 
15
 
Overload current value
 
Igfh
 
0.5 ~ 100A
 
 
16
 
Overload time delay setting
 
tIgfh
 
0.1 ~ 99.99S
 
 
17
 
Charging protection
 
Charging time protection automatically exit
 
tCD
 
0.01 ~ 9.99S
 
 
18
 
White cast back control charging protection
 
Icdnf
  
19
 
White charging current value
 
Icd
 
0.5 ~ 100A
 
 
20
 
White charging delay setting
 
tIcd
 
0.01 ~ 9.99S
 
 
Note :. 1 Ifsx values ​​have the following meanings :
0 : Exit 1 to 3 : Inverse - 1: General , 2 : very , 3: Extreme
. 2 Igfhnf values ​​have the following meanings :
0 : Exit 1 to 2: inputs - 1: Alarm 2 : Trip
3.3 device parameter tuning
No.
 
Name
 
Symbol
 
Range
 
1
 
Device -level management
 
The mailing address of the device
 
ADDR
 
1 ~ 110
 
2
 
Operation of the device password
 
PASSWORD
 
0 to 99
 
3
 
Baud Rate
 
Baud Rate Setting
 
BTL
 
0 to 9
 
4
 
Exchange amount ratings
 
CT primary current rating
 
Sec.IN
 
0 ~ 65535A
 
5
 
PT primary current rating
 
Sec.UN
 
0 ~ 999.9KV
 
4 . Protection Principle wiring diagram